What you need before you start
- Fiber fusion splicer, charged, with clean V-grooves and electrodes
- Precision cleaver
- Jacket and coating strippers
- Isopropyl alcohol (99% or better) and lint-free wipes
- Heat-shrink splice protection sleeves
- Splice tray or enclosure, and a container for fibre offcuts
- OTDR or light source and power meter to test the finished splice
Step-by-step fusion splicing
- 1Run the splicer's arc calibration when you start the day or arrive at a new site, especially after moving between altitudes.
- 2Slide a heat-shrink sleeve onto one of the two fibres now. Forgetting it means breaking the finished splice and starting again.
- 3Strip the cable jacket and buffer to expose the 250 µm coated fibre, then strip the coating to bare glass over the length your cleaver and holder need.
- 4Clean the bare fibre with alcohol on a lint-free wipe, pulling in one direction. From here, do not let the clean glass touch anything.
- 5Cleave the fibre at the length marked for your splicer's holder. A precision cleaver gives a flat, square end face.
- 6Place the fibre in the splicer's holder or V-groove without touching the cleaved tip. Repeat steps 3 to 6 for the second fibre.
- 7Close the wind cover and start the splice. The machine images both ends, checks the cleave angle, aligns the fibres and fuses them with an electric arc.
- 8Read the estimated loss on the screen. If it is high, or the machine reports a cleave or alignment error, redo the splice rather than accept it.
- 9Open the cover gently, slide the sleeve over the joint so it sits centred, and place it in the heater.
- 10When the heat cycle ends, let the sleeve cool, then lay it in the splice tray and coil the spare fibre in generous loops.
Reading the fusion splicer's screen
The estimated loss is a calculation from the image, not a measurement, but it is a reliable early warning. These are the problems a splicer most often reports and what usually causes them:
| What you see | Usual cause | Fix |
|---|---|---|
| Cleave angle error | Worn or dirty cleaver blade, or fibre not seated flat | Clean the cleaver, rotate the blade position, recleave |
| Bubble or dark spot in the joint | Dust or alcohol residue on the fibre end | Clean again, let alcohol evaporate, recleave |
| Splice looks thin or thick | Arc power wrong for the conditions | Run arc calibration and repeat |
| High estimated loss | Dirty V-grooves, poor cleave or mismatched fibre types | Clean V-grooves, recleave, check both fibres are the same type |
| Fibre breaks when the cover opens | Glass touched something after cleaning | Restrip, clean and recleave |
FTTH splicing: drops, pigtails and splitters
In an FTTH build, most fusion splicing happens in three places: feeder and distribution cables joined in closures, pigtails spliced onto cable fibres in ODFs and fibre access terminals, and drop cables joined at the customer end. Flat FTTH drop cable needs the right holder or careful preparation before it will sit in the splicer. Splice-on SC/APC connectors let you terminate a drop with a fusion splice and a factory-polished end face, which gives lower loss than a fast connector.
Keep a record of each splice by closure and tray. When a subscriber goes offline months later, that record is what lets a crew find the right fibre quickly.
Test every splice with an OTDR
The splicer's estimate is not proof. An OTDR shows the real loss at each splice and its distance along the cable. Test from both ends and average the two readings, because a single-direction OTDR reading can show a splice as a small gain or an exaggerated loss when two fibres differ slightly.
Safety and good habits
- Put every glass offcut in a sealed container; fibre shards are hard to see and easy to push into skin
- Wear eye protection and do not eat or drink at the splicing table
- Clean the V-grooves and fibre clamps at the start of each day
- Replace electrodes when the manufacturer's arc count is reached or splice quality drops